A lightning strike near a Moorabbin home took out a TV, two appliances, and damaged the solar inverter. Kenny installed Type 1 and Type 2 surge protection devices at the switchboard, covering the entire home including the solar circuit.
What the Client Needed.
A storm the previous week had produced a nearby lightning strike that sent a voltage surge through the home's electrical system. The result: a 65-inch TV, a dishwasher control board, and a chest freezer all needed replacing. The 5kW solar inverter was also showing fault codes and had stopped exporting.
The client's insurer covered the appliance damage but made it clear that future claims would be more difficult to pursue without documented surge protection in place. They wanted the best available solution installed before another storm season.
Kenny assessed the existing switchboard and confirmed it had space for both Type 1 and Type 2 SPDs, providing protection against direct lightning strikes on the supply network as well as smaller internal surges. The solar inverter circuit was included in the protection scope.
How Kenny
Got It Done
Switchboard Assessment & Damage Check
Switchboard inspected for surge damage to wiring or breakers. A burnt neutral connection was found and repaired before the SPDs were installed.
Type 1 SPD Installed at Main Incomer
Voltex Agardio Type 1 surge protection device installed at the main incomer, provides protection against external surges from the supply network including indirect lightning strikes.
Type 2 SPD Installed Across Circuits
Voltex Type 2 SPD installed across the busbar to protect all downstream circuits from internal surges caused by switching of large appliances or residual transients.
Full Test & Certificate Issued
All circuits tested under load. SPD indicator lights confirmed active. Certificate of Electrical Safety issued. Written report provided for the client's insurance file.

Job Details
& Outcomes.
- Type 1 and Type 2 surge protection covering all circuits in the home
- Burnt neutral connection identified and repaired during the install
- Certificate of Electrical Safety issued for insurance documentation
- Written installation report provided for the client's insurer